List of Holding Registers
Network Data
Func.
Code
Name R/W Description
Reg. Range Res.
A020 Multi-speed 0 setting R/W Defines the first speed of a
multi-speed profile, range is 0.0 /
start frequency to 400 Hz
A020 = Speed 0 (1st motor)
1029h 0 / start
freq. to
4000
0.1 Hz
A220 Multi-speed 0 setting
2nd motor
R/W Defines the first speed of a
multi-speed profile, range is 0.0 /
start frequency to 400 Hz
A220 = Speed 0 (2nd motor)
150Fh 0 / start
freq. to
4000
0.1 Hz
A021 Multi-speed 1 setting R/W 102Bh
A022 Multi-speed 2 setting R/W 102Dh
A023 Multi-speed 3 setting R/W 102Fh
A024 Multi-speed 4 setting R/W 1031h
A025 Multi-speed 5 setting R/W 1033h
A026 Multi-speed 6 setting R/W 1035h
A027 Multi-speed 7 setting R/W 1037h
A028 Multi-speed 8 setting R/W 1039h
A029 Multi-speed 9 setting R/W 103Bh
A030 Multi-speed 10 setting R/W 103Dh
A031 Multi-speed 11 setting R/W 103Fh
A032 Multi-speed 12 setting R/W 1041h
A033 Multi-speed 13 setting R/W 1043h
A034 Multi-speed 14 setting R/W 1045h
A035 Multi-speed 15 setting R/W
Defines 15 more speeds,
range is 0.0 / start frequency to
400 Hz.
A021= Speed 1...
A035 = Speed 15
1047h
0 / start
freq. to
4000
0.1 Hz
A038 Jog frequency setting R/W Defines limited speed for jog,
range is 0.00 / start frequency
to 9.99 Hz
1048h 0 / start
freq. to
999
0.01 Hz
A039 Jog stop mode R/W Define how end of jog stops
the motor; three options:
00...Free-run stop
01...Controlled deceleration
02...DC braking to stop
1049h 0, 1, 2
A041 Torque boost select R/W 104Ah
A241 Torque boost select,
2nd motor
R/W
Two options:
00...Manual torque boost
01...Automatic torque boost
1510h
0, 1
A042 Manual torque boost
value
R/W 104Bh
A242 Manual torque boost
value, 2nd motor
R/W
Can boost starting torque
between 0 and 20% above normal
V/f curve,
range is 0.0 to 20.0%
1511h
0 to 200 0.1 %
A043 Manual torque boost
frequency adjustment
R/W 104Ch
A243 Manual torque boost
frequency adjustment,
2nd motor
R/W
Sets the frequency of the V/f
breakpoint A in graph (top of
previous page) for torque boost,
range is 0.0 to 50.0%
1512h
0 to 500 0.1 %
A044 V/f characteristic curve
selection
R/W 104Dh
A244 V/f characteristic curve
selection, 2nd motor
R/W
Two available V/f curves;
two select codes:
00...Constant torque
01...Reduced torque
06...Reduced torque1
1513h
0, 1, 6
A045 V/f gain setting R/W 104Eh
A245 V/f gain setting, 2nd
motor
R/W
Sets voltage gain of the inverter,
range is 20. to 100.%
1514h
20 to 100 1 %