What do I do if there is an Error 53 on the display?
What do I do if the baery icons on the display don’t match
the number of baeries I have?
What do I do if there is an Error 19 on the display?
• This is low ambient temperature protecon mode. Raise
the ambient temperature to above 5
o
C.
• Put the BMS in detecon mode.
• Conrm all modules are ON with a green light around
the ON/OFF switch.
• Wait unl the modules count matches the screen.
• Conrm the address of the modules are set according to
the Install Manual page 11.
• This a parallel detecon mode fault. If the system is in
parallel, please check the communicaon cable between
the master baery system and the connected baery
systems in parallel.
• Set inverter DIP switches to parallel detecon mode to
rediscover the paralleled baery system.
• Set the parallel stack to the appropriate address (see pg
12 of the Install Manual).
What do I do if there is an Error 20 on the display?
How do I get the BMS to communicate with a Sol-Ark inverter?
The display is not on, but the power buon is on/pushed in.
How do I connect to the app?
What do I do if my baeries are ashing?
What do I do if there is an Error 15 on the display?
• Check that the modules are addressed correctly (see
pages 14-15).
• Check rmware is up to date.
• Conrm baery module detecon was completed.
• Conrm the inverter communicaon cable is plugged
into the INV-CAN port of the BMS and the baery CAN
BUS on the inverter.
• If you didn’t use our provided cable, please follow the
pin guide on page 29 of the Install Manual when making
your own inverter communicaon cable.
• Firmware could be outdated or mismatched.
• Power cycle your rst module, then power on the BMS.
• See the app secon of the Install Manual (page 19)
• Slow ash: Update the enre stack to the latest
rmware.
• Fast ash: System needs to be balanced by discharging
and charging to 100% SOC.
• There is cell damage on one of the cell packs. Call Tech
Support for assistance.
Common Quesons + Soluons