Panel Operation
BC-200 Manual – P/N DOC-01-013 35
7.3.3.7.1.1 Service Menu – List – List – Analog – Detectors – Status
This screen will show a reading of the selected Analog addressable detector updated every 3 seconds, 255 times.
The detector’s current configuration is displayed together with “live readings” as shown below.
L1D2 (Z001) > APARTMENT 1 BATHROOM
Poll Mode > FlashScan Mode
Programmed As > HEAT
Actual Device > HEAT
Device State > NORMAL
Device Status > NORMAL
LED Status > Polling
Detector Values:
Alarm = 0% Peak Temperature = 30 C
Temperature = 24 C Day Alm Sensitivity= 5
Night Alarm Sens = 1
Device Scanned 255 Times .
A = 0
F = 0
I = 0
N = 0
20 JULY 2002 14:44:37
PREV
TEST Menu
DAY MODE
NEXT RESET
L1D3 (Z990) > APARTMENT 1 BEDROOM
Poll Mode > FlashScan Mode
Programmed As > PHOTO-OPTICAL
Actual Device > PHOTO-OPTICAL
Device State > NORMAL
Device Status > NORMAL
LED Status > Polling
Detector Values: (Needs Cleaning)
Alarm = 0% Peak Alarm Value = 10%
Prealarm = 0% Day Alm Sensitivity = 5
Compensation = 81% Day PreAlarm Sens = 5
Night Alarm Sens = 1
Night PreAlarm Sens = 1
Device Scanned 255 Times .
A = 0
F = 0
I = 0
N = 0
DAY MODE
PREV
TEST MenuNEXT RESET
Note: “:Zxxx” is displayed after the descriptor, xxx is the zone number mapped to the detector. A zone number of 0
is an indication that the detector is not mapped to a zone.
Actions:
Press the PREV buttons to move to the previous installed point.
Press the NEXT buttons to move to the next installed point.
Press the TEST button to enter test menu for the detector.
Press the RESET button to re-initialise the detector.
Press MENU to return to the Analog Menu screen.
Explanations of terms:
Poll Mode CLIP Shows the current polling protocol being used. CLIP = 1 detector
at a time. Polling mode is auto sensed at start-up
Programmed As 8 Types Detector type programmed into panel
Actual Device 8 Types Detector type physically seen on loop.
Device State Normal/Active/Alarm Shows alarm or activated condition of point.
Device Status 23 fault types Detailed description of fault condition. i.e.: “No Response”
LED Status 4 Types Polling, On, Off, Polling ID
Alarm % Current Percentage of alarm or Degree Celsius
Pre-alarm % Current Percentage of Pre-alarm
Peak Alarm Value % or
C Highest reading since last reset.
Drift Compensation % Please refer to page 107 for information on Drift Compensation.
Sensitivities 1-9 Detector sensitivity for day/night, alarm/pre-alarm. Please refer to
page 104 for explanation information on sensitivity settings.