Section 11 - W7220 JADE™ Economizer Module
117 Honeywell Economizers 63-8594-02
Fig. 11.
Menu Parameter
Param-
eter
Default
Value
Parameter
Range and
increments
Notes
STATUS IN CO2 _ _ _
ppm
0 to 2000
(3500) ppm
Displays value of measured CO2 from CO2
sensor. Invalid if not connected, short or out-of-
range. May be adjusted in Advanced menu by
Zero offset and Span
DCV STATUS n/a ON/OFF Displays ON if above setpoint and OFF if below
setpoint, and ONLY if a CO2 sensor is connected.
DAMPER OUT 2.0V 2.0 to 10.0 V
Displays output position to the damper actuator.
ACT POS n/a 0 to 100% Displays actual position of actuator.
ACT COUNT n/a 1 to 65,535 Displays number of times actuator has cycled. 1
Cycle equals the sum of 180° of movement in any
direction.
ACTUATOR n/a OK/Alarm
(on Alarm
menu)
Displays Error if voltage or torque is below
actuator range
EXH1 OUT OFF ON/OFF Output of EXH1 terminal. ON = 24 Vac Output;
OFF = No Output.
EXH2 OUT OFF ON/OFF Output of AUX1 O terminal Displays ON when
damper position reaches programmed percentage
setpoint ON = 24 Vac Output, OFF = No Output;
displays only if AUX1 O = EXH2
ERV OFF ON/OFF Output of AUX1 O terminal, ON = 24 Vac Output,
OFF = No Output; displays only if AUX1 O = ERV
MECH COOL ON 0 0, 1, or 2 Displays stage of mechanical cooling that is
active.
FAN SPEED n/a LOW or
HIGH
Displays speed of fan on a 2-speed fan unit
W (HEAT IN) n/a ON/OFF Displays status of heat on a 2-speed fan unit.
SET-
POINTS
MAT SET 53ºF 38 to 70 ºF;
increment by
1
Setpoint determines where the economizer will
modulate the OA damper to maintain the mixed
air temperature.
LOW T LOCK 32ºF -45 to 80 ºF;
increment by
1
Setpoint determines outdoor temperature when
the mechanical cooling cannot be turned on.
Commonly referred to as the Compressor lockout.
DRYBLB SET 63ºF 48 to 80 ºF;
increment by
1
Setpoint determines where the economizer will
assume outdoor air temperature is good for free
cooling; e.g.; at 63 ºF unit will economizer at 62 ºF
and below and not economize at 64 ºF and above.
There is a a 2 ºF deadband.
Table 3. Menu Structure

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Design and Application and is the answer not in the manual?

Honeywell Design and Application Specifications

General IconGeneral
BrandHoneywell
ModelDesign and Application
CategoryController
LanguageEnglish

Related product manuals