EasyManua.ls Logo

Honeywell Design and Application - W7212, W7213 and W7214

Honeywell Design and Application
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 3 - Types of Analog Economizers
63-8594-02 Honeywell Economizers 36
W7212, W7213 and W7214
The W7212 DCV economizer logic module
was the simplest Demand Control Ventilation
economizer model. It combined all of the
benefits of the W7459 and W7210 with the
added features of the W7215. It did not
include shutdown, air change and purge but
had an “N” terminal for occupancy. On W7213
and W7214 models the N terminal was a B or
O terminal for use with heat pumps.
There were three models:
W7212A- Used with series 70 actuators
including DCA’s, M7215, and Modutrol
Motors
W7213A - Used with heat pumps or
conventional rooftop units. B terminal
energized in heating and unenergized in
cooling
W7214A - Used with heat pumps or
conventional rooftop units. O terminal
unenergized in heating and energized in
cooling.
All models were panel mounted or directly
mounted to M7215 motor.
Commercial
thermostat
One enthalpy or dry bulb and
one mixed/supply air sensor
required. Second enthalpy
sensor optional.
W7212, W7213
and W7214 install
on flat surface or
mount on M7215
motor.
Optional room CO
2
sensor on A models,
additional optional
outdoor CO
2
sensors
on B models.
Series 62 or 72 Direct
Coupled Actuators
or M7215 Actuator

Table of Contents

Related product manuals