Section 8 - W6215, W7215 And W7460 Economizer Modules
75 Honeywell Economizers 63-8594-02
Carbon Dioxide Sensor Setup
For applications where factory configurations
do not meet the application requirements the
sensor may be re-configured by the installer to
meet most configuration needs.
Most installers prefer to use a C7632 CO
2
sensor that does not need to be programed or
adjusted when installed.
CO2
Sensors Display No Display A1 Output A2 Output
Wall Mount
With Relay
C7242A1030 C7242A1048 0 Vdc = 500 ppm
(2 Vdc = 800 ppm) and
10 Vdc = 2,00 ppm
Relay Output:
0 to 800 ppm = Open,
More than 800 ppm = Closed,
Reopens at less than 700 ppm
Wall Mount C7242A1014 C7242A1022 Analog Sensor Mode:
0 Vdc = 500 ppm
(2 Vdc = 800 ppm) and
10 Vdc = 2,000 ppm
Time interval = 2 seconds
Duct Mount C7242B1012 C7242B1020
Outside Air Not Available C7232E1007