Section 1 - Ventilation
Honeywell Economizers 63-8594-02 16
Example 3: Minimum Ventilation Adjustment
1. Specifications:
Office space - 100,000 ft
2
Air handler capacity 20,000 cfm
(566 m
3
/min.)
People in area - 250
2. Ventilation (V
OT
) required:
= 250 x 5 cfm + 0.06 cfm/ft
2
x 100,000 ft
2
= 1250 cfm + 6000 cfm
= 7250 cfm
Where V
at
= 0.06 cfm/ft
2
x 100,000 ft
2
.
Therefore V
at
= 6000 cfm
3. Ventilation percentage:
7250 cfm (205.3 m
3
/min)/20,000 cfm
(570 m
3
/min)
V
OT
maximum position= 36%
6000 cfm (169.9 m
3
/min)/20,000 cfm
(570 m
3
/min)
V
OT
Minimum position= 30%
4. Measure the return air temperature:
73°F (23°C).
5. Measure the outside air temperature:
30°F (-1°C).
This example shows a procedure for adjusting
the DCV maximum and minimum positions.
OUTSIDE
A
IR
30˚F (-1 C)
EXHAUST
AIR
DAMPER
M23910
DAMPER
RETURN
AIR
73˚F (23 C)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Design and Application and is the answer not in the manual?

Honeywell Design and Application Specifications

General IconGeneral
BrandHoneywell
ModelDesign and Application
CategoryController
LanguageEnglish

Related product manuals