Section 11 - W7220 JADE™ Economizer Module
109 Honeywell Economizers 63-8594-02
ROOF TOP UNIT
Y1O
Y2O
Y1I
Y2I
OCC
24 VAC
1K1
1K1
E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
CO2
SENSOR
2-10 VDC
(OPTIONAL)
MA
MA
OAT
OAT
C R
M28980C
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
AUX1-0
AUX2-I
OA TEMP
SENSOR
20K NTC
M7215
NOTE THAT THE C7250 20K NTC SENSOR CAN BE MOUNTED IN THE OAT ONLY IN THIS CONFIGURATION.
1
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O
OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
2
3
3
1
MA TEMP
SENSOR
20K NTC
+
-
TR1
TR
IN
IN
2
R(+)
C(-)
Wiring Application Examples
This section describes the wiring
configurations for the JADE™ Economizer
system. The configurations are:
—“Stand-alone Economizer”
—“Economizer with Sylk Bus Sensors” on
page 116
Stand-alone Economizer
The most basic configuration is the stand-
alone Economizer (see Fig. 4 and Fig. 6). A
stand-alone Economizer is directly wired to
sensors, actuators, thermostat, and
mechanical controls in the roof top unit. It does
not require Sylk Bus communications.
Fig. 4. Stand-alone dry bulb Economizer configuration with black motor M7215.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Design and Application and is the answer not in the manual?

Honeywell Design and Application Specifications

General IconGeneral
BrandHoneywell
ModelDesign and Application
CategoryController
LanguageEnglish

Related product manuals