Network Graphic Annunciator (NGA) Operations Guide P/N 9020-0675:B1 03/21/13 37
View Screen (Devices Tab) View Screen
10.5 View Screen (Devices Tab)
The Devices tab of the View screen allows the display of some of the settings pertaining to the SLC
devices of any ILI-MB-E3 or ILI-S-E3, ILI95-MB-E3 or ILI95-S-E3 on the network.
Figure 10.5.1
illustrates the screen that appears when the user selects the Devices tab from the View screen.
Figure 10.5.1 View Screen (Devices Tab)
View Screen
(Global Tab) Options
Description
I/O Devices Displays PAS Night Bypass and the Multilevel Alert and Action
percentages.
NACs Displays the NAC delay settings (such as the NAC Cutoff Delay
and the Silence
Inhibit Delay). The Silencing and Coding settings for each NAC
circuit also display.
System ID Displays the nineteen (19), character System ID label that appears
below this header.
Miscellaneous
Options
Displays the Multi-trouble Acknowledge, Trouble Reminder, Walk
Test Timeout, PM-9 Supervision and DACT Supervision settings.
Annunciators Displays the number of ASM-16 switch modules, ANU-48 LED
annunciator drivers, LCD-E3 displays and LCD-7100 annunciators
connected to the selected ILI-MB-E3. Since the ILI-S-E3 and
ILI95-S-E3 nodes do not support annunciators, switch modules or
displays, these nodes will always be reported as zero when
viewing configuration information from the ILI-S-E3 nodes.
Baud Rate Displays the currently configured RS-232 baud rate for the
selected node in a pop-up window.
UP / DOWN Use the up and down arrows to scroll through the list of available
nodes.
X Press the "X" button in the upper right corner to close this screen.
Table 10.4.1 View Screen (Global Tab) Controls