2.General
2.1Technicaldata
TechnicaldataHONCOCON13twinstream :
Medium : alltypesofgasesexceptforSulphur‐containinggases(H
2
S).
StationsforgaspressurereductionofgasescontainingSulphur
areavailableonrequest.
Inletpressure(p
1
) : maximum20bar(ANSI150)
Outletpressure(p
2
) : minimum20mbar(2kPa)
MinimalΔp(p
1
‐p
2
) : 0.5bar
Temperaturerange(ambient) :‐20°Cto+60°C
Flowcoefficient : Cgvalue(EN334)435
Regulatingcapacities : seesizingtables
Totalweight : about300kg
Cartridgeweight : about40kg
Packedvolume : about1.5m
3
Length : maximum1435mm(incl.header)
Width : maximum860mm
Height : maximum980mm
Inletconnection : 2”
Outletconnection : 4”
Pressurerating : accordingtoANSI150
Impulselineconnection : metricfittingsaccordingtoDIN2353
Pressuregauges : 2or3,formeasuring
inlet,(intermediate)andoutletpressure.
Pressuregauge : ¼"BSPthread
Regulatortype : two‐pathpilotoperatedspringloadedclosedgaspressure
regulator
Shutoffvalvetype : directactingsafetyshutoffdevice(SSD)withintegralpressure
equalizing.(Pushbuttontype)
Filter : cartridgefilterwithsupportcage
Filter
material : felt
Filterfineness : 3micron(0,003mm)
Safetydevices
Safetydevice : SSDvalvewithSSDcontroller
Locationoftypeplates
Casing : beneathpitcover
Unit : onmembranecover
Pilots : onthesideofthepilot
Informationontypeplates
Casing : namemanufacturer,
typespecification,serialnumber,maximum
operationpressure,yearofconstruction
Unit : namemanufacturer,typespecification,serialnumber,maximum
operationpressure,minimalreducedpressure,yearof
construction
Pilots : namemanufacturer,typespecification,springtype,serial
number,adjustmentdata,yearofconstruction,maximum
allowedinletpressure