Thehingedpitlidcover(10)isfittedwithastainlesslatchthatissecurelypluggedforthepreventionofunauthorized
entry.
Anisolatingballvalve(09)ismountedtotheinletofthecasing.Whenthisballvalveisopen,itshandleprevents
removalofthePlexiglascover.
Adust
filter(07)isconnectedunderthecartridge.
Thegasthenpassesthroughasafetyshut‐offdeviceupstreamoftheregulatorwithinthemodularcartridge:
‐ Thedeviceconsistsofassdvalve(06)andassdcontroller(03).Thecontrollersitsontopofthecartridge.If
theregulatorfails
intheopenposition,therelaywilldetectanincreaseinlinepressureandreleasethe
spring‐loadedvalve,cuttingoffthegassupply.Itisalsofittedwithamanualemergencyreleasebutton.
Gaspressurereductionisachievedbyapilotoperated,diaphragmregulator(05).
Therequiredoutletpressure
issetandcontrolledwiththepilot.
Avalve(11)isattachedtotheoutletflange.Thevalvecanbeoperatedwithoutremovingthecoverofthecasing.
However,asasafetyfeature,ifthisvalveisopen,thenitisnotpossibletoremovethisPlexiglascover.
Theinstallationof
areliefvalveisanoption.
Transducerscanbeinstalledintheprotectionoftheenclosedspace,fortheremotemeasurementofpressures.Close
indicationoftheslamshutvalvebymeansofaproximityswitchisalsoavailable.
Thestationisfittedwithtwopressuregaugeswhichreadthe
inletandoutletpressures.Thesegaugesaresituated
undertheprotectionofthePlexiglascoverbutarevisiblewhenthepitlidcoverisopened.
Purgevalvesfordepressurizationoftheunitaremountedonthecartridge.
Ahandleisattachedtothecartridge,sothecartridgecanbeeasilyremoved
fromthecasing.