Model IFP-2100/ECS Installation Manual LS10143-001SK-E
9-13
SUP DET
PHOTO Latching
Non Latching
Use this option when you want a detector to indicate a supervisory
alarm.
ION
HEAT
PHOTO DUCT
ACCLIMATE
HEAT HT
PHOTO-HEAT
BEAM
CO SMOKE
DETECTOR
CO ALRM /
FIRE ALRM
No Accessory, Sounder base, Relay Base Intelligent Sounder base.
CO ALRM /
FIRE SUPR
CO SUPR /
FIRE ALRM
CO SUPR /
FIRE SUPR
Latching
Non Latching
Supervisory switches can be latching or non-latching.
W-
DETECTOR
PHOTO Wireless photoelectric detectors.
ACCLIMATE
(IDP)
Wireless acclimate photoelectric detector.
PHOTO-HEAT
(SK)
Wireless heat detector.
HEAT
W-SUP DET
Same as W-
Detector
Latching
Non Latching
Wireless photoelectric detectors.
SWITCH
MANUAL PULL Use this switch type for manual pull stations. This input is always
latched. The switch can clear only when an alarm is reset. This switch
type has the highest fire priority; it overrides any other type of fire
alarm.
WATERFLOW Latching Use this switch type for monitoring water flow in a sprinkler system.
Switch closure will cause a sprinkler alarm. Water flow switches can be
programmed as latching or non-latching.
You can program a delay of up to 90 seconds to be used with a water
flow switch. The delay allows for normal, brief changes in sprinkler
system water pressure. The water flow alarm will not activate unless
the switch is active for the programmed delay time.
If a delay is used, the system begins counting down when the switch
closes. If the switch opens (restores) before the timer expires, a water
flow alarm is not generated. If the water flow switch remains closed
after the timer expires, a water flow alarm will be generated.
Non Latching
FIRE SUPER-
VISORY
Latching Use this switch type for tamper monitoring of sprinklers and other fire
protection devices. If a contact closes, a sprinkler supervisory event will
be generated. Supervisory switches can be latching or non-latching.
Non Latching
FIRE DRILL System-level, non latching switch. This switch is an alternative way of
causing a fire drill. It has the same operation as the fire drill option
available from the annunciator. When the switch is activated, a fire drill
begins; when the switch is de-activated, the fire drill ends.
SILENCE This system-level switch is an alternative way to silence the fire
system. It has the same effect as pressing the Silence key.
RESET This system-level switch is an alternative way to reset the fire system.
It has the same effect as pressing the Reset key.
Table 9-5: Programming Options for 6815 Modules
Type
Selection
Function Latching Option Comments