EasyManua.ls Logo

Honeywell IFP-2100ECS - Class a Notification Wiring

Honeywell IFP-2100ECS
264 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LS10143-001SK-E Control Panel Installation
4-34
2. Configure the circuit through programming (see Section 9.5)
Figure 4-47 Class B Notification Appliance Circuit Wiring
Maximum voltage drop is 3V per Class B notification. See Table 4-4.
4.15.1.2 Class A Notification Wiring
You must use an appliance from the list of compatible appliances in Appendix A at the back of this manual.
To install a Class A notification appliance circuit:
1. Wire the Class A notification appliances as shown in Figure 4-48.
Table 4-4: Maximum Impedance Class B
Current Maximum Impedance
1.0A 3Ω
1.5A 2Ω
2.0A 1.5Ω
2.5A 1.2Ω
3.0A 1.0Ω
Caution!
For proper system supervision do not use looped wire under terminals marked O and X of the Flexput
connectors. Break wire runs to provide supervision of connections.
power limited supervised
notification wiring
regulated 24 VDC
3A per circuit, 9A max combined
4.7 kΩ
EOL
alarm polarity shown

Table of Contents

Other manuals for Honeywell IFP-2100ECS

Related product manuals