LS10143-001SK-E Before You Begin Installation
3-18
2. If using 24 VDC aux power only. No standby or alarm current for battery calculation if using 24VAC, 120VAC or 240VAC.
3. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed
during that time. However, during normal operation, door holders draw current and must be included in the 9.0A total current
that can be drawn from the panel.
4. Use next size battery with capacity greater than required.
5. Maximum SBUS address capacity is 63 SBUS modules. The practical limit is determined by the amount of SBUS bandwidth
consumed by each SBUS module. See section 4.13.2.
6. The FACP can only support 2 devices w/LED’s on. The current draw has been added to the panels alarm current.