There is a demanding or important guest that wants to be able to set Room Target
temperature to a higher or lower value than what is currently selectable on the e7w.
Solution:
Place the room HVAC controller into “Limited Energy Management” (LEM) mode.
Then Inncom thermostat/HVAC partner to the e7w supports a “Limited Energy Management” mode where the
thermostat turns off most energy savings algorithms and expands the guest selectable upper and lower target
temperature range. This can be enabled in a room that has a demanding guest that requires more flexible room
temperature control than what is normally allowed for a room.
LEM mode in the e7w HVAC partner can be enabled or disabled from the e7w using a 3 button sequence.
To Enable LEM mode in the HVAC partner from the e7w :
1. Press and Hold the Mode button
2. Press and Release the Fan button
3. Press and Release the Up Arrow button
4. Release the Mode button
5. - - - followed by LE.n (LEM) will appear on the e7w display, indicating the command to enable
LEM mode for 72 hours was sent to the e7w HVAC partner.
Note: LEM mode in the HVAC partner will automatically turn OFF after 72 hours. In thermostats/HVAC
controllers that have been shipped recently (contact Inncom for details) , LEM mode will
automatically clear when the room is Checked-Out from the front desk (if the hotel is networked
with a PMS system installed).
To manually Disable LEM mode in the HVAC partner from the e7w :
1. Press and Hold the Mode button
2. Press and Release the Fan button
3. Press and Release the Down Arrow button
4. Release the Mode button
5. - - - followed by nO.r (normal mode) will appear on the e7w display, indicating the command to
disable LEM mode was sent to the e7w HVAC partner.