4. Press MODE to check the PAn value.
5. Press UP arrow button to display rF mode or press FC to return the INITIALLIZATION MODE.
Setting the RF Channel during Initialization
1. After rF is displayed, press MODE (26 default rF value is displayed)
2. Use UP/DOWN arrows to change value (range is 11-26).
3. Press FAN, the unit beeps to confirm the value stored in the memory and display back to rF.
4. Press MODE to check the rF value.
5. Press FC to return the INITIALIZATION MODE.
After returning INITIALIZATION MODE, e7w display a Target Temperature value on the display screen. Then e7w begins to
communicate with the default address of its HVAC Partner using the defined Room ID, RF Channel and PAN ID. Default
INNCOM HVAC partner address is 14.