F
!
Value
You cannot change the e7w displayed target temperature, Fan Speed or HVAC Mode and a
warning triangle symbol is displayed
Possible Reasons:
The e7w has been placed into “Contractormode. When the e7w has been placed into Contractor mode , it
locks its target temperature to a defined value and locks out the e7w buttons. This is feature is intended to
be used during the hotel construction phase to set the room to a defined target temperature and prevent
tampering.
To exit the e7w out of Contractor mode:
1. Enter SERVICE MODE
2. Press UP/DOWN arrow buttons to select Ctr - -
3. Press MODE button. This action displays “-“ and Value.
4. Press FAN button to turn off CONTRACTOR MODE. After turning off CONTRACTOR MODE e7w play beep
sound.
5. Press the FC button twice to exit SERVICE MODE
The alert icon should clear