INTELLIGUARD 9000
74-3047114
MOUNT MOM
To mount the MOM:
1.
At the selected mountin
g
location, remove the MOM
cover.
2.
Use a No. 1 Robertson
(
s
q
uare drive
)
screwdriver to
remove the screws securin
g
the circuit board to the
back casin
g
.
IMPORTANT
Touch a grounded object to ensure you are not elec-
trostatically charged before handling the circuit
board.
3.
Gentl
y
remove the circuit board. Be sure not to touch
an
y
of the circuits or terminals.
4.
Mount the MOM on the wall usin
g
four No. 6 round or
pan head screws.
NOTE: Feed the re
q
uired cables into the MOM base usin
g
the two s
q
uare holes in the base wirin
g
channel, or
remove the knockouts on either end of the wirin
g
channel and pass the cables throu
g
h the openin
g
s.
5.
Replace the circuit board.
6.
Connect the wires to the MOM as shown in Fi
g
. 14.
7.
Repeat steps 1 throu
g
h 6 for each MOM.
8.
When installation is complete and power is applied,
learn the MOM.
NOTE: Steps 8a. throu
g
h 8k. ma
y
be replaced b
y
usin
g
the
PRO 9000 software. See the Commission section,
steps 1a. throu
g
h 1c. for more information.
a. Make sure the LED DS1 on each installed MOM dis-
pla
y
s
C
.
b. From each MOM, press the
S2
switch
(
ACCEPT
)
button to place each MOM in the COMMUNICA-
TION STATUS displa
y
mode.
c. The center se
g
ment
(
RECEIVE
)
of the LED displa
y
(
DS1
)
flashes to indicate incomin
g
data.
d. The decimal point on the LED displa
y
(
DS1
)
of each
MOM is off.
e. From the CC2 Mode menu, select
1-CONFIG
to
enter the CONFIGURATION
menu.
f. From the CC2, select
1-LEARN
to enter the
LEARNING menu.
g
. From the CC2, select
2-DEVICES WITH SERIAL #
to start the learnin
g
process. The CC2 displa
y
s
Searching
. The decimal point on the LED displa
y
(
DS1
)
li
g
hts on each MOM to indicate that the
MOMs are in the learnin
g
mode.
h. From each MOM, press and hold the
S2
(
ACCEPT
)
button for approximatel
y
two seconds, or until the
bottom se
g
ment
(
TRANSMIT
)
of the LED displa
y
DS1 flashes and the decimal point turns off. When
the decimal point disappears, the device is learned.
NOTE: If the MOM was previousl
y
learned, the decimal point
would have turned on and off almost immediatel
y
.
i. When the
ACCEPT
ke
y
is pressed on the CC2, the
I9000 exits the learnin
g
mode and displa
y
s the total
number of devices known b
y
the s
y
stem includin
g
the MOMs.
j
. From the CC2, exit the CONFIGURATION menu for
chan
g
es to become effective.
k. The bottom se
g
ment
(
TRANSMIT
)
of the LED dis-
pla
y
(
DS1
)
on each MOM flashes ever
y
time each is
polled
(
addressed
)
. The center se
g
ment
(
RECEIVE
)
also flashes.
9.
Confi
g
ure each output in the MOM, as needed. See
Output Parameters and Pro
g
rammin
g
section.
10.
Cause an alarm on the input that is linked to the corre-
spondin
g
output to be tested. If a Hold-up Actuator was
pressed durin
g
the test, a
RESET DETECTORS
com-
mand is re
q
uired to clear the latched alarm.
(
The out-
puts ma
y
onl
y
be tested when the I9000 pro
g
rammin
g
is
completed
)
.
11.
Repeat steps 1 throu
g
h 10 for each MOM.
12.
Replace each MOM cover.
OUTPUT PARAMETERS AND PROGRAMMING
The MOM has nine pro
g
rammable parameters:
Parameter 0 = Display
0 =Displa
y
is not active when tamper is closed.
1 = Displa
y
remains active when tamper is closed.
Parameters 1 to 8 = Outputs 1 to 8 respectively
Each output can be confi
g
ured for one of three different t
y
pes:
0 = Output is normall
y
off, output turns on when activated.
1 = Output is normall
y
on, output turns off when activated.
2 = Output is normall
y
off and be
g
ins pulsatin
g
when
activated.
Programming
1.
Press
S3 (QUIT)
to return to
C
on the LED displa
y
.
2.
Press
S1 (NEXT)
until the LED displa
y
flashes
P
.
3.
Press
S2
to accept pro
g
ram mode.
4.
Press
S1
to scroll throu
g
h the parameters to output 1.
No decimal point is displa
y
ed.
5.
Press
S2
to be
g
in pro
g
rammin
g
for output 1. A decimal
point appears in the bottom ri
g
ht corner of the LED dis-
pla
y
to indicate the present output t
y
pe number.
6.
Press
S1
to scroll to the desired output t
y
pe number
(
if
different from output t
y
pe number displa
y
ed in step 5
)
.
7.
Press
S2
to accept the displa
y
ed output t
y
pe and to dis-
pla
y
the next parameter number.
8.
Repeat steps 4. throu
g
h 7. for each output.
9.
Press
S3
to leave the pro
g
ram mode.
COMMUNICATION AND OUTPUT FUNCTION STATUS DISPLAY
The MOM has three displa
y
modes:
P
allows the user to confi
g
ure the individual outputs.
C
enters the Communication Displa
y
mode and causes the
center bar
(
RECEIVE
)
on the LED displa
y
to li
g
ht each
time the MOM receives communication with the CU. The
bar closest to the terminal
(
TRANSMIT
)
li
g
hts whenever
the MOM responds.
A
enters the Output Function Status Displa
y
mode. The
number of the active output functions is displa
y
ed. If more
than one output is active, the displa
y
scrolls and shows
each active output for one second. When there are no
active outputs, the center bar on the seven se
g
ment LED
li
g
hts.
Other Detection Devices and Outputs
I9000 accepts connections to detection and warnin
g
devices
not included with the s
y
stem; however, these devices must
conform to the re
q
uirements found in form no. 74-3035,

Other manuals for Honeywell INTELLIGUARD 9000