INTELLIGUARD 9000™
74-3047—128
APPENDIX B
DEVICE WORKSHEET
Fig. 23. Device power worksheet.
QTY DEVICE DESCRIPTION UNIT POWER TOTAL POWER
CU
CC2 MAXIMUM OF 4 (NO BACKLIGHTING)
KID (MAXIMUM OF 8)
HEDS IV
BIC-2 OR BIC-2 HU (1 INPUT AND 1 LOGICAL OUTPUT)
BIC-2 OR BIC-2 HU (1 INPUT AND 1 OPTIONAL RELAY OUTPUT)
BIC-6 (6 PROGRAMMABLE INPUTS AND OUTPUTS)
MOM (MAXIMUM OF 8 PROGRAMMABLE LOGIC OUTPUTS)
RRI (REQUIRED FOR EBI RS-485 MULTI-DROP WIRING CONFIGURATIONS)
(45)
(10)
CC2 MAXIMUM OF 4 (WITH BACKLIGHTING)
(98)
(20)
(8)
(6)
(10)
(45)
(85)
M16260C
TOTAL POWER REQUIREMENTS FOR THIS INSTALLATION A
B
C = B - A
D
C + D
POWER AVAILABLE FROM PANEL (ISP = 800 mA)
SUBTOTAL (SHOULD BE POSITIVE +) IF NOT, ADD POWER AT "D"
IF TOTAL "C" IS NEGATIVE, ADD POWER SUPPLY (RIPS) (ISP = 800 mA)
TOTAL
(25)
1
1
EACH ISP HAS TWO POWER OUTPUTS (AUX 1 AND AUX 2). THE LOAD CONNECTED TO ONE ISP OUTPUT MUST NOT EXCEED 400mA.
2
COMBINATION OF CC2s WITH BACKLIGHTING AND CC2s WITHOUT BACKLIGHTING-FOUR TOTAL MAXIMUM.
2
2