INTELLIGUARD 9000™
3 74-3047—1
Fig. 2. I9000 CU connected to devices, EBI.
General Procedure
Plan the System
1.
Review the
ob file, plans and specifications for accu-
rac
and completeness.
2.
Prepare an
necessar
installation drawin
s
for exam-
ple, risers
.
3.
Determine an
necessar
connections to other s
s-
tems.
4.
Select the devices for the s
stem.
5.
Select the location for each device and point.
6.
Calculate the power re
uirements.
NOTE: Be sure to include the input concentrator and motion
detector power re
uirements in the power suppl
and batter
calculations.
Install the System
1.
Pull the wires.
2.
Mount the e
uipment.
3.
Connect the wires to each input device, output device,
and point.
NOTES:
— All device terminals accept 24 to 18 AWG
0.27
s
mm to 1.0 s
mm
conductors.
— Alwa
s use twisted pair cables for the local bus.
Install the local bus usin
multi-drop topolo
.
Maximum distance for the local bus is 3277 ft
999m
.
— Maximum input loop distance for ULI/ULC appli-
cations is 50 ft
15m
.
— Maximum input loop distance for non-ULI/ULC
applications is 250 ft
75m
.
4.
Set the address of the devices with address switches.
5.
Record the local bus number, device t
pe, address and
serial number for each device.
6.
Check to make sure that the wirin
matches the
ob dia-
ram.
7.
Connect power to each RIPS and CU.
8.
Measure the volta
e and current draw on each power
circuit.
System Checkout
1.
Check the volta
e on each device.
2.
Set the loop confi
uration and other parameters for
each device.
3.
Make sure all input loops are confi
ured for input.
4.
Make sure all loops are normal
not in trouble or alarm
.
5.
Make sure the alarm condition responds properl
.
6.
Make sure the trouble condition responds properl
.
1
2
5
6
TB1
1
2
3
4
TB1
I9000
ISP AND CU
ICP
– +– +
1
2
3
4
– +
1
2
3
4
– +
1
2
3
4
– +
1
2
3
4
– +
1
2
3
4
– +
1
2
3
4
– +
1
2
3
4
– +
1
2
3
4
– +
1
2
3
4
– +
HEDS IVCC2
1
2
3
4
– +
BIC-2 HU
BIC-2
1
2
3
4
– +
MOM
MOM
1
2
3
4
– +
RIPS
RIPS
KID
KID
BIC-6
BIC-6
COM 1
31 DEVICES
MAX. CABLE 3277 FT
RS-485
COM 2
31 DEVICES
MAX. CABLE 3277 FT
RS-485
EBI
COM 3
RS-232 (RS-485 WITH RRI)
M14461A
A GROUND CONNECTION BETWEEN THE CONTROL UNIT AND ALL RIPS SHARING COM 1 AND/OR COM 2 IS REQUIRED AS
A GROUND REFERENCE. TO PREVENT GROUND LOOPS, ONLY MAKE ONE GROUND CONNECTION.
1
1
1