INTELLIGUARD 9000
3 74-30471
Fig. 2. I9000 CU connected to devices, EBI.
General Procedure
Plan the System
1.
Review the
j
ob file, plans and specifications for accu-
rac
y
and completeness.
2.
Prepare an
y
necessar
y
installation drawin
g
s
(
for exam-
ple, risers
)
.
3.
Determine an
y
necessar
y
connections to other s
y
s-
tems.
4.
Select the devices for the s
y
stem.
5.
Select the location for each device and point.
6.
Calculate the power re
q
uirements.
NOTE: Be sure to include the input concentrator and motion
detector power re
q
uirements in the power suppl
y
and batter
y
calculations.
Install the System
1.
Pull the wires.
2.
Mount the e
q
uipment.
3.
Connect the wires to each input device, output device,
and point.
NOTES:
All device terminals accept 24 to 18 AWG
(
0.27
s
q
mm to 1.0 s
q
mm
)
conductors.
Alwa
y
s use twisted pair cables for the local bus.
Install the local bus usin
g
multi-drop topolo
gy
.
Maximum distance for the local bus is 3277 ft
(
999m
)
.
Maximum input loop distance for ULI/ULC appli-
cations is 50 ft
(
15m
)
.
Maximum input loop distance for non-ULI/ULC
applications is 250 ft
(
75m
)
.
4.
Set the address of the devices with address switches.
5.
Record the local bus number, device t
y
pe, address and
serial number for each device.
6.
Check to make sure that the wirin
g
matches the
j
ob dia-
g
ram.
7.
Connect power to each RIPS and CU.
8.
Measure the volta
g
e and current draw on each power
circuit.
System Checkout
1.
Check the volta
g
e on each device.
2.
Set the loop confi
g
uration and other parameters for
each device.
3.
Make sure all input loops are confi
g
ured for input.
4.
Make sure all loops are normal
(
not in trouble or alarm
)
.
5.
Make sure the alarm condition responds properl
y
.
6.
Make sure the trouble condition responds properl
y
.
1
2
5
6
TB1
1
2
3
4
TB1
I9000
ISP AND CU
ICP
+ +
1
2
3
4
+
1
2
3
4
+
1
2
3
4
+
1
2
3
4
+
1
2
3
4
+
1
2
3
4
+
1
2
3
4
+
1
2
3
4
+
1
2
3
4
+
HEDS IVCC2
1
2
3
4
+
BIC-2 HU
BIC-2
1
2
3
4
+
MOM
MOM
1
2
3
4
+
RIPS
RIPS
KID
KID
BIC-6
BIC-6
COM 1
31 DEVICES
MAX. CABLE 3277 FT
RS-485
COM 2
31 DEVICES
MAX. CABLE 3277 FT
RS-485
EBI
COM 3
RS-232 (RS-485 WITH RRI)
M14461A
A GROUND CONNECTION BETWEEN THE CONTROL UNIT AND ALL RIPS SHARING COM 1 AND/OR COM 2 IS REQUIRED AS
A GROUND REFERENCE. TO PREVENT GROUND LOOPS, ONLY MAKE ONE GROUND CONNECTION.