INTELLIGUARD 9000
5 74-30471
Fig. 3. Sample wiring architecture.
BIC-2 HU
HOLD-UP
INPUT CONCENT.
62 MAX.
BIC-2
INPUT CONCENT.
62 MAX.
BIC-6
INPUT CONCENT.
62 MAX.
HEDS IV
HALL EFFECT
DOOR SWITCH
62 MAX.
CC2
KEYBOARD
CONTROL CENTER
4 MAX.
KID
AREA
KEYPAD
8 MAX.
MOM
MULTIPLE
OUTPUT MODULE
8 MAX.
RIPS
INTELLIGENT
POWER SUPPLY
7 TOTAL MAX.
POWER COM 1 COM 2
ISP
POWER
SUPPLY
CU
CONTROL
UNIT
SERIAL
PORT
TO EBI.
THIS PORT IS
ALSO USED
FOR PRO9000
PROGRAM
LOADING
50 FEET
EARTH
GROUND
50
FEET
EARTH
GROUND
1
1
ONE ISP IS SHIPPED WITH EACH CU AND RIPS.
HONEYWELL I9000 SYSTEM WIRING
M14462A
NOTES:
A TOTAL OF EIGHT ISPs CAN BE CONNECTED TO THE CU. THIS INCLUDES THE ISP
LOCATED IN THE CONTROL UNIT PLUS THOSE IN THE RIPS.
THE CU SUPPORTS A MAXIMUM OF 31 DEVICES PER COM PORT (31 FOR COM 1
AND 31 FOR COM 2, TOTAL = 62).
SPLITTING DEVICE TYPES EQUALLY BETWEEN COM 1 AND COM 2 IMPROVES
SYSTEM PERFORMANCE. EXAMPLE: TWO CC2s ON COM 1 AND TWO OTHERS
ON COM 2, THREE BIC-6s ON COM 1 AND THREE OTHERS ON COM 2.