1. Testing Hold-Up Actuators
ACTION MESSAGE SIGNAL
Press
ID ? –
Enter your ID #. ID ? # #
CODE ? – – – –
Enter your CODE #. TEST MENU 2 BEEPS
HOLD UP TEST
NOTE 1: The test period lasts seven minutes.
Hold-up actuators automatically reset at the end of the test.
To accept
HOLD-UP TEST, press
AREA ? –
Enter the AREA # for HOLD-UP TEST 2 BEEPS
which you want hold-up 1 BEEP EVERY
actuator testing. Flashing 2 SECONDS
NOTE 2: “HOLD-UP # # “ indicates the ID number of the tested actuator.
This actuator remains displayed until a new actuator is activated or
until the test period is ended.
Activate other
HOLD-UP TEST 2 BEEPS
hold-up actuators.
HOLD-UP # #
Flashing
NOTE 3: Repeat the procedure for all hold-up actuators you wish to test.
To exit
HOLD-UP TEST, press
END-H-U TEST BEEPING AT
FASTER RATE
NOTE 4: At the end of the hold-up test, all actuators are automatically reset.
Any further testing results in a FALSE POLICE DISPATCH.
TEST MENU
HOLD-UP TEST
To exit, press
** INTELLIGUARD 9000 **
yy/mm/dd hh:mm
TEST
TESTING
TESTING