MA-2000
22 M-167.1-MA2000-EN / 06.2022
6.3 Relay outputs
FUNCTION CHARACTERISTICS
Sounder 1 contact controlled by 24 Vcc / 1 A resistive
USR2 Max 1 A resistive 30 V DC, NO / NC or supervised output 1 A Fused, selectable through
Jumper JUSR2 (refer to basic board topography)
USR1 Max 1 A resistive 30 V DC, NO / NC or supervised output 1 A Fused, selectable through
Jumper JUSR1 (refer to basic board topography)
General Alarm Max 1 A resistive 30 V DC, NO / NC or supervised output 1 A Fused, selectable through
Jumper JALL (refer to basic board topography)
General Fault Max 1 A resistive 30 V DC, NO / NC or supervised output 1 A Fused, selectable through
Jumper JGST (refer to basic board topography)
6.3.1 Instructions to setting the relay outputs as NO / NC or Supervised