MORLEY-IAS ZX Fire Alarm Control Panels
Page 6 Document No. 996-175-000-1, Revision 01 Commissioning Manual
Key Legend Symbol Function
0 to 9 Press to enter numbers 0-9 or letters A-J (N-W with Shift)
> Press to scroll through fire alarms or faults manually on the display or
letter K (X with Shift)
< Press to scroll back through fire alarms or faults manually on the
display or letter Z (Y with Shift)
Change
ZM
Press to change a display option (where allowed)
or letter M (Z with Shift)
Enter
Press to confirm entry of a multiple digit number
No
Press to answer No, or terminate a display option
Yes
Press to answer Yes, or step through a display option
Shift
Press to show user options on the display
Press, during programming, to allow entry of Letters N-Z
Table 2 – Alphanumeric and Interactive Control Keys
• The control keys are disabled at USER LEVEL 1. Pressing the SHIFT key will cause the display to
prompt for entry of the Level 2 password. The password must be entered to re-enable the control keys
at Level 2.
3.2 Front Panel LED Indications
• The Level 1 LED Indicators are divided
into two sections.
• The upper array of LED Indicators shows
the operational conditional of the panel
and the installation.
• The lower array of Zone LED indicators
shows the location of a fire alarm or fault.
• The standard Zone LED Indicators
provide identification for up to 20 zones.
On the ZX5Se and ZX10Se panels, this
can be extended by adding either a further
20 zones (to give a total of 40 zones) or a
further 60 zones (to give a total of 80
zones).
• The LED Indicators illuminate as red,
yellow or green to give a clear indication
of the panel status as follows:
FIR
FAUL
System / CPU Faul
cknowledge
Earth Faul
Disablemen
Tes
Sounder Faul
Delayed Mode
Relays Disable
Powe
Supply Faul
larms Silence
Sounders Disable
Figure 3 – System Control LED Display