MORLEY-IAS ZX Fire Alarm Control Panels
Page 58 Document No. 996-175-000-1, Revision 01 Commissioning Manual
16.5 Hochiki Multi-Sensor Support
The Hochiki Multi-Sensor is supported as detailed below from panel software version 824 onwards.
Previously, from version 698, the multi-sensor was partially supported – operating as an optical smoke
device becoming more sensitive with temperatures above 40 °C.
Where the control panel is in normal operation or sensitivity day mode is invoked, the multi-sensor
mode and threshold parameters can be modified according to the specific site requirements. This
allows a different mode of operation at different times of the day (see Section 11.3 Sensitivity Mode).
For each multi-sensor address, in the edit device menu, choose to ‘edit thresholds’. Firstly, the mode
of operation will be presented. Select 0 for multi-mode, 1 for optical-smoke only mode or 2 for heat
only mode. Normal threshold set-up will follow. These settings will take effect on a device by device
basis throughout the day mode period (where sensitivity mode is programmed).
Where night mode is invoked (as part of sensitivity day mode), the device operates in the multi-sensor
mode providing the control panel with an analogue value representing a combination of the smoke
and heat elements of the sensor. The pre-alarm threshold is fixed at 45 and the full-alarm threshold at
55.
16.6 System Sensor/ Morley-IAS Multi-Sensor & Laser Support
16.6.1 System Sensor/ M-IAS Multi & Laser Diagnostics
When viewing the device from the user menus, the meaning of the analogue value is as follows:
Value displayed Multi laser
0 No device No device
1 Mid-range invalid Mid-range invalid
2 Mid-range invalid Mid-range invalid
3 Mid-range invalid Mid-range invalid
4 Mid-range invalid Mid-range invalid
4 or 7 Out of range Out of range
5 Low chamber trouble Drift alert 0.3%
10 Maintenance alert Maintenance alert
15 Maintenance urgent Drift alert 0.6%
20 initialising Initialising
29 multi / 32 laser Normal Normal
50 multi / 50 laser Level 1 alarm Level 1 alarm
64 multi / 57 laser Level 2 alarm Level 2 alarm
79 multi / 64 laser Level 3 alarm Level 3 alarm
93 multi / 71 laser Level 4 alarm Level 4 alarm
107 multi / 79 laser Level 5 alarm Level 5 alarm
121 multi / 86 laser Level 6 alarm (HEAT) Level 6 alarm
- / 93 laser - Level 7 alarm
- / 100 laser - Level 8 alarm
- / 107 laser - Level 9 alarm
System Sensor Multi-sensor & Laser Diagnostics