EasyManua.ls Logo

Honeywell Morley-IAS ZX Series - Networks Option; Panel Networks; Network - Panel Network Address; Standard Network Settings for Shared Zones

Honeywell Morley-IAS ZX Series
65 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ZX Fire Alarm Control Panels MORLEY-IAS
Commissioning Manual Document No. 996-175-000-1, Revision 01 Page 49
13 Networks Option
Network options define the way in which the panel is configured to operate on a networked system.
These options, such as the panel address, should be checked when a system is first installed, but will
rarely need changing after this time.
The network can operate as either a ‘Shared Zone’ or ‘Report and Control’ network. A summary of the
network options for various network configurations is given below. Refer to the Network Interface
Guide (P/N 996-075) for detailed information.
Press ’3’ to select the ‘Network’ option from page 3 of the Commission menus.
To change a setting, press either CHANGE or ‘No’ and then enter the desired setting. Move on using
the ‘Yes’ key.
13.1 Panel Networks
13.1.1 Network - Panel Network Address
The Network Address will have been set to ‘1’ when the panel leaves the factory. If the panel is to be
installed as part of a networked system the address may need to be changed – each panel must have
a unique network address in the range 1 to 99. If the panel is not required on a network, then this
address must be left at ‘1’.
Each panel should be given a unique panel address number.
[ Panel in Commissioning mode ]
---------------------------------------------
Panel Network-address number = 1 ?
13.1.2 Standard Network Settings for Shared Zones
The following tables give typical settings for a ‘shared zone’ mini-network system.
Network Option Option setting Comments
Panel network-address number 1 to 99 Enter slave panel address, i.e. 3.
Quantity of slave processors 0 Number of slaves connected to port C.
(DO NOT CHANGE).
Use modem [TRUE]/[FALSE] Set to TRUE if a modem is connected to port C.
Share zones [TRUE]/[FALSE] Zones are shared between panels
Peer-to-Peer [TRUE]/[FALSE] Pass MUTE / ACCEPT, SILENCE / RESOUND and RESET
key presses back to master.
Port B Protocol * 0 Use default of 0 unless special application interface
System events [GLOBAL]/[LOCAL] Global -
1. Passes system events over network
2. Accepts other network events.
Local -
1. Does not pass events over the network.
2. Ignores other network events.
NOTE: The zoned fire status is passed over a shared-zone
network regardless of events being global or local.
Table 12 – Slave Panel Network Settings
* Port B is not available on ZX1Se or ZX2Se panels.

Table of Contents

Related product manuals