MORLEY-IAS ZX Fire Alarm Control Panels
Page 40 Document No. 996-175-000-1, Revision 01 Commissioning Manual
9 Power Supplies Option
• This option displays the current state of the AC Mains and Battery supplies.
• Should a fault occur and the AC Mains fail, the backlighting on the alphanumeric liquid crystal display
will be turned off to conserve battery power.
• To select the option, press ‘3’ from page 2 of the Commission menus.
10 Passwords Option
• This option allows the number of User Level 2 passwords and the value of each password to be defined.
• To select the option, press ‘4’ from page 2 of the Commission menus. The display then prompts the
number of User Level 2 passwords allowed.
[ Panel in Commissioning mode ]
---------------------------------------------
Number of passwords = 1?
• Up to ten User Level 2 passwords can be assigned and used.
• Press ‘Yes’ to accept the number of passwords and step on. Press No if the number of passwords is
incorrect. Then enter the required number using the number keys.
• The display then prompts the value of the first User Level 2 password as follows:
[ Panel in Commissioning mode ]
---------------------------------------------
Password 1 = 1234 ?
• Press ‘Yes’ to accept this value and step on to the next password.
• Press Change and then enter the new number using the number keys to assign a new code value.
Caution: When changing the password DO NOT use ‘0’ as the first digit.
• Repeat for each password. When all passwords have been accepted or changed, the display prompts
the period that the panel should remain in Level 2 (without a key being pressed) before automatically
inhibiting the keys and returning to User Level 1.
[ Panel in Commissioning mode ]
---------------------------------------------
Max level 2 time = 15 minutes ?
• Press ‘Yes’ to accept this value and return to the commission menu. Alternatively, change the value
as required. The default time is 5 minutes.
Access level 2 timeout can be cancelled by entering a value of ‘0’. Use this option with
extreme care, as it is BS5839 or EN54-2 non-compliant to leave the panel in state where it
is possible to be operated by a ‘non-responsible’ person.