MORLEY-IAS ZX Fire Alarm Control Panels
Page 40 Document No. 996-175-000-1, Revision 01 Commissioning Manual
9 Power Supplies Option
This option displays the current state of the AC Mains and Battery supplies.
Should a fault occur and the AC Mains fail, the backlighting on the alphanumeric liquid crystal display
will be turned off to conserve battery power.
To select the option, press ‘3’ from page 2 of the Commission menus.
10 Passwords Option
This option allows the number of User Level 2 passwords and the value of each password to be defined.
To select the option, press ‘4’ from page 2 of the Commission menus. The display then prompts the
number of User Level 2 passwords allowed.
[ Panel in Commissioning mode ]
---------------------------------------------
Number of passwords = 1?
Up to ten User Level 2 passwords can be assigned and used.
Press ‘Yes’ to accept the number of passwords and step on. Press No if the number of passwords is
incorrect. Then enter the required number using the number keys.
The display then prompts the value of the first User Level 2 password as follows:
[ Panel in Commissioning mode ]
---------------------------------------------
Password 1 = 1234 ?
Press ‘Yes’ to accept this value and step on to the next password.
Press Change and then enter the new number using the number keys to assign a new code value.
Caution: When changing the password DO NOT use ‘0’ as the first digit.
Repeat for each password. When all passwords have been accepted or changed, the display prompts
the period that the panel should remain in Level 2 (without a key being pressed) before automatically
inhibiting the keys and returning to User Level 1.
[ Panel in Commissioning mode ]
---------------------------------------------
Max level 2 time = 15 minutes ?
Press ‘Yes’ to accept this value and return to the commission menu. Alternatively, change the value
as required. The default time is 5 minutes.
Access level 2 timeout can be cancelled by entering a value of ‘0’. Use this option with
extreme care, as it is BS5839 or EN54-2 non-compliant to leave the panel in state where it
is possible to be operated by a ‘non-responsible’ person.