Page 50 Document No. 996-175-000-1, Revision 01 Commissioning Manual
Network Option Option setting Comments
Panel network-address
number
1 to 99 Enter Master’s own address, e.g.. 4.
Quantity of slave
processors
1 to 99 Number of slaves DIRECTLY connected to the Master, i.e.
via port C.
Slave CPU 1 is at
network address
1 to 99 The address of the first slave panel.
Slave CPU 2 is at
network address
1 to 99 The address of the second slave panel.
Etc.
Use modem [TRUE]/[FALSE] Set to TRUE if a modem is connected to port C.
Share zones [TRUE]/[FALSE] Zones are shared between panels
Peer-to-Peer [TRUE]/[FALSE] Allow MUTE / ACCEPT, SILENCE / RESOUND and RESET
key presses from a slave panel.
Port B Protocol * 0 Use default of 0 unless special applications interface.
System events [GLOBAL]/[LOCAL] Global -
1. Passes system events over network
2. Accepts other network events
Local -
1. Does not pass events over the network.
2. Ignores other network events
NOTE: The zoned fire status is passed over a shared-zone
network regardless of events being global or local.
Table 13 – Master Panel Network Settings
For full information on how to commission and program a network installation, refer to
document P/N 996-075.
13.2 Port B Protocols
NOTE: * Port B Protocol is not available on ZX1Se or ZX2Se panels.
The Port B serial interface supports a number of different protocols.
These can be used to define the connections as:
1. Standard MORLEY-IAS Panel Network / Graphics PC Interface
2. Pager Interface
3. Other PC System Interface
The following table defines the settings to be entered for each interface type.