MORLEY-IAS ZX Fire Alarm Control Panels
Page 42 Document No. 996-175-000-1, Revision 01 Commissioning Manual
11 Day Mode Option
• Page 3 of the Commission menus is shown below:
[ Panel in Commissioning mode ]
---------------------------------------------
1)Day mode 2)Setup options 3)Network [1]
4)Events 5) Talk To Slave
1
This option is displayed if the panel is networked to a slave panel.
• Press ‘1’ to select the ‘Day Mode’ option from page 3 of the Commission menus.
The DAY MODE option and all sub-menu options require the Memory Lock to be open.
11.1 Day Modes
• The display then shows three possible day mode options:
[ Panel in Commissioning mode ]
---------------------------------------------
1)Delayed mode 2)Sensitivity mode
3)Verification mode
• The panel can be commissioned to automatically invoke different operating modes according to the
time of day.
• Each mode has adjustable start and finishing times. Outside of the designated start and finishing
times, the panel reverts to normal operation. If required, a mode can be set independent of time by
setting the start to ‘00:00’ and finish to ‘24:00’.
• The operating modes available are summarized in the table below.
Operating
Mode
Description
Delayed mode
During the day/night the alarm signal from detectors is immediately recognized and
identified on the panel display, but no outputs turn on until stage1/stage2 timers have
expired. Call points / Pull Stations override this mode.
Sensitivity mode
Allows smoke and temperature detectors to use different pre alarm and fire alarm
thresholds during the day/night.
Verification
mode
Allows smoke detectors to tolerate transient alarms according to the programmed
verification delay time during either day or night.
Table 10 – Day Mode Options
• Configure each mode by selecting it from the day mode menu.