MORLEY-IAS ZX Fire Alarm Control Panels
Page 54 Document No. 996-175-000-1, Revision 01 Commissioning Manual
14.1.3 Define Event Outputs
• All output devices can have two system events directly assigned to them.
• A relay style device will turn on if either of the assigned events occurs.
• A sounder style device will turn on if the primary event occurs, (Shown as ‘Event-A’), or will pulse if
only the secondary event occurs (‘Shown as Event-B’).
• The ‘Define outputs’ display option allows the events assignments to be inspected and changed if
required.
It strongly recommended that a PC be normally used to define events.
• Press the ‘No’ key to terminate this display option.
15 Normal Operation
• The panel is placed in its normal operating state by selecting ‘NORMAL OPERATION’ from page 1 of
the Commissioning menu. Press ‘3’ to select the function.
• Once this is done the panel will perform a reset and then become fully active. The alphanumeric
display may prompt for entry of the time and date – enter the correct time and date as appropriate.
• Refer to the User Manual for further information on the operation and functions available at User
Levels 1 and 2.
Remember to lock the memory.
If the memory lock switch is left in the open position for an extended period of time the panel will report a
‘CONFIG MEMORY’ fault. Refer to Section
8 for further information.