MORLEY-IAS ZX Fire Alarm Control Panels
Page 28 Document No. 996-175-000-1, Revision 01 Commissioning Manual
Pressing any key then restores the display to the normal commissioning menu.
The Auto Learn sequence can be used as many times as required and does not affect the text
description used to describe the location of each sensor.
Always verify that the system has found all devices correctly. Use the ‘Devices’ option to
obtain detailed information on the device type and to see the address of each device
found on the loop.
5.3.2 Calibrate
The calibrate function is identical to the routines described in Signalling Loops Section. Refer to
Section
5.2.2.
5.3.3 Zones
The Zone function is identical to the routines described in Signalling Loops Section. Refer to Section 5.2.3.
5.3.4 Devices
The ‘Devices’ option presents detailed information for the various types of peripheral device fitted on
the bus.
[ Panel in Commissioning mode ]
---------------------------------------------
P:012 Z003 "BOILER ROOM "
Input unit S= 16 D8..D1= 00000001
The signal from the peripheral device is fixed at 16. It will drop to 0 if communications or
power to it is lost.
5.3.4.1 Changing Device Information
Changes are made by first pressing the ‘Change’ key. The display will present a menu of options that
can be changed, as follows:
[ Panel in Commissioning mode ]
---------------------------------------------
1)Sensor Text 2)Zone 3)Event
6)Action 7)Group 9)Mode
Select the required option by pressing the appropriate number. Press the ‘No’ key to return to the
normal, device information display.
If only the device text can be changed, the display will jump straight to the location text.
A
ddress Zone Location Text
Device Type
A
nalogue Signal Digital inputs status
1=Logic High 0=Logic Low