ZX Fire Alarm Control Panels    MORLEY-IAS 
 
Commissioning Manual  Document No. 996-175-000-1, Revision 01  Page 15 
5 Configure Option 
5.1  Accessing the Configure Option 
•  Page 1 of the Commission menu is shown below: 
 
 [ Panel in Commissioning mode ] 
---------------------------------------------- 
1)CONFIGURE          YES)More Options  [1] 
2)Inspect              3)NORMAL OPERATION 
 
•  The CONFIGURE option allows the Signalling Loops, peripherals, sounders and relays to be 
programmed. It also enables the function to allow the panel to be programmed by a PC. 
•  Press ‘1’ to select the ‘CONFIGURE’ option. 
 
 
The CONFIGURE option and all sub menu options require the Memory Lock to 
be open. 
 
•  The display then shows a menu of options as follows: 
 
  [ Panel in Commissioning mode ] 
----------------------------------------------
 CONFIGURE : Loop 1) 2) 3) 4) 5)  [1] 
 6)Peripherals  7) Sounders 8)Relays  9)PC 
 
NOTE: The menu will only show the number of signalling loops programmed during setup (Refer to the Setup 
Option). The ZX2Se can only have two loops maximum. 
5.2 Signalling Loops 
•  After selecting a loop from the configure menu, the display will present a list of options as follows: 
 
 [ Panel in Commissioning mode ] 
---------------------------------------------- 
 CONFIGURE : Loop 1)  1)Zones  [1] 
 2)Devices   3)Auto Learn  4)Calibrate 
 
 
The words ‘CONFIGURE: Loop 1’ on the top line of the menus provides a reminder that 
panel is in configuration mode, with loop 1 selected. 
 
•  Select the required option by pressing the appropriate numeric key. 
•  When commissioning a new panel, start by performing an ‘Auto Learn’. This will cause the panel to 
search for all devices installed on the loop.