ID3000 Series Installation & Commissioning Manual
Installation - Panel Electronics
33 997-274-000-6, Issue 6
September 2009
5.7.1 Fitting the Replacement Base PCB
10 Taking suitable anti-static precautions and with the
replacement Base PCB orientated correctly, offer it to
the main chassis PCB enclosure. With the locating holes
on the PCB lined up with the hank-bush studs, guide
the Base PCB into position.
11 Using a No.1 Posidriv screwdriver starting with the top
left corner, gently fix each of the seven (7) M3 x 10 SEM
screws from step 8 screw in turn and then secure.
DO NOT over-tighten.
Note: Set the link settings on the replacement PCB to
those noted in step 8.
12 Re-fit all PCBs removed in steps 5, 6 and 7 above.
Re-fit the main chassis in the back box - using the
reverse of the main chassis removal procedure.
13 With all items replaced and wiring and cabling
re-terminated, reconnect earthing cables,
mains power first and then the batteries to the panel.
i. Power sockets, SK8 and SK12 (from PSU
or DTP).
ii. Data socket, SK1 (from Processor PCB).
iii. Loop Cabling connectors, TB6 and TB7
(Loops 1 & 2).
iv. Fault and Fire Relay sockets, TB8 and TB9.
v. Cover Off connector, SK10 (not used).
vi. Auxiliary sockets, TB4 and TB5.
vii. Input socket, TB3 (Input 1 only supported
for VdS configuration).
viii. Output Sockets, TB1 and TB2.
ix. Comms sockets (A and B), SK2 and SK3
(from Isolated RS485 Interface PCB or
Printer RS232 Interface PCB, if fitted).
x. Loop Cabling connector, SK4 (from Loops
3 & 4 Interface PCB, if applicable).
xi. Loop Cabling connector, SK6 (from Loops
5 & 6 Interface PCB, if applicable).
xii. Loop Cabling connector, SK7 (from Loops
7 & 8 Interface PCB, if applicable).
xiii. RS232 Off-line Configuration PC
Connector, SK11.
xiv. Zone Expansion Socket, SK9 (refer to
Section 5.5).
The selection of sounders or volt-free
contacts, and normally-open or
normally-closed, is described in
Section 7.7. For volt-free contacts
(outputs 3 & 4 only) the ‘-ve’ terminal
is common.
8
L
8
8
8
8
8
8
10
11
11
11
11
11
11
8
11
i.
i.
ii.
SK8
SK1
SK12
9
10
1
3
1
5
10
15
20
25
30
32
A
2
4
C
1 2
iii.
+1- +2-
+ 1 - + 2 -
+3- +4-
+ 3 - + 4 -
iii.
iv. iv.
OUTPUTS1&2
OUTPUTS3&4
+-+ -
+ - + -
+- + -
+ - + -
+- +-
+ - + -
+-
+ -
+-
+ -
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
vi. vi.
vii
viii.viii.
SK4
SK9
SK11
2
3+4
3 + 4
5+6
5 + 6
7+8
7 + 8
16
15
1
1
2
1
9
10
5
6
9
x.
xiii.
xiv.
SK6
2
16
15
1
xi.
SK7
2
16
15
1
xii.
SK3
2
2
14
14
13
13
1
1
14
14
13
13
SK2
SK2
2
2
1
1
1
2
ix.
S/No.
S /
No.
LOOP 1
LOOP 2
INPUTS 1 & 2
INPUTS 1 & 2
AUX
AUX
1
2
FAULT
FIRE
BASE PCB
124-361
1
1
2
2
RS232
Base PCB PN: 124-361
5.7.2 Cables & Wiring
Disconnect/reconnect the following from the Base PCB:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier ID3000 Series and is the answer not in the manual?

Honeywell Notifier ID3000 Series Specifications

General IconGeneral
BrandHoneywell
ModelNotifier ID3000 Series
CategoryControl Panel
LanguageEnglish

Related product manuals