ID3000/ID2000 Fire Panel Configuration Tool Manual
Panel Settings
2 - 19
6 If Day Mode is required to be cancelled
automatically, set the end times (up to two
per day) using the Time-of-day program
(see Section 5). This does not comply
with EN54. There are no start times; Day
Mode cannot be started automatically.
Manual methods of cancellation (the DAY
MODE pushbutton or Input 2) remain
available if automatic cancellation is
configured.
EN54-2: 9.1.2
Disablement and re-
enablement MUST be a
manual operation at
Access level 2.