EasyManua.ls Logo

Honeywell Notifier ID3000 - 2.7 Tests Tab

Honeywell Notifier ID3000
147 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
997-291, Version 3.05
November 2010
ID3000/ID2000 Fire Panel Configuration Tool Manual
Panel Settings
2 - 14
2.7 Tests Tab
This window sets Automatic Sensor Test and
Walk Test parameters. Edit as follows:
1 Set which day of the week analogue sensor
tests will occur, or ‘Daily’ if every day, or
select ‘Not set’ if these tests are not required.
2 If a day of the week or ‘Daily’ was set in
step 1, use the spin buttons to set the time
of day at which the test is to start.
3 Select what happens when a Manual Call
Point (MCP) is set into alarm during a walk
test. The options are for the MCP to operate
the sounders for either:
a. A 1 second pulse, or
b. Continuously while the MCP remains in
alarm (‘Follows MCP’).
4 If required, set an automatic timeout for walk
test (range 1-720 minutes). To maintain
EN54 compliance, set to 0 (no timeout).
EN54-2: 10.1 (b)
Tests must be started and
stopped manually.
5 If required, a RESET action can be applied
at the end of a zone walk test. Tick the box
to select this function.
1 2 3
4
5

Related product manuals