Copyright © 2022 Honeywell International Inc. All rights reserved.
point (it can be at one end of the controller or detector, but not at the same time). By default,
a resistance of 270 ohm (RL) is connected between the detector terminals. Before
connecting with the controller, remove the resistor.
If the RAEGuard Lite transmitter you purchase supports the HART function, connect it to the
HART terminal by referring to the following figure:
5.2) Terminals
Note: When wiring, open the top cover of the detector in advance and pull out the circuit
modules such as the display and the mainboard.
5.3) Cable connection
Note: All cables or connections on the transmitter must be sealed with certified plugs or
glands!
Industrial grade armored cables are recommended for RAEGuard Lite connection cables.
RAEGuard Lite gas detector needs the power supply between 16VDC and 32VDC provided
by the controller or upper system. For the cable connection distance, please read the “User’s