Page 30 SLN 700 SmartLine NCR Level Transmitter User’s Manual Revision 1
4.20 Low DK
When the LCD displays 4.20, press to enter the DK value
adjustment setting menu. Display in LCD is as follows.
Press again to enter the DK value adjustment menu.
Press key to select “Yes”, used for the measuring setting when
DK value is low (<=2.1).. Display in LCD is as follows.
At this time, it is necessary to manually input an accurate empty tank
span value, which is used to determine the position of the tank bottom to
reduce the reflection of the tank bottom.
4.21 Dust or
Agitation
Agitation state of material (liquid) Dust state of material (solid)
4.22 Echo
Lost Timeout
Device will send out failure signal after setting time if there’s no echo
signal being received. Default setting is 300s.
Low DK
Y
Distance
Y
N
Low DK
Low DK