OPERATOR MANUAL // SECTION 1: TECHNICAL DESCRIPTION
HONEYWELL 13
1.6 Testing
Special Conditions for Testing
The SS4 Detector should be tested immediately after installation, after
repair or maintenance involving wiring or module replacement, after
periodic maintenance, or after lens contamination has been identified.
Automatic Testing
Automatic SLR-BIT (Built In Test) “through-the-lens” self-testing is
performed, during Detector operation, for virtually all-internal electronic
systems at the selected Test Period (Section 1.5, 3). One of the Red LEDs
will remain illuminated (Fault) to indicate contamination of the window lens,
missing the protective Self-test grill, or when removing the enclosure cover.
1.6.3 Manual Testing
For manual testing, the SS4-A/-A2 Detectors may be exposed to an actual
industry standard open flame or to a Test Lamp simulating a fire. It is
mandatory to use the Honeywell Analytics handheld UV/IR Test Lamp
Model No’s FT-2045 or FT-2145 with SS4 Fire Detectors. The FT-2045 and
FT-2145 Test Lamps are housed in an Explosion-Proof enclosure, powered
by internal rechargeable batteries, and designed for indoor and outdoor
use. For additional information on the Test Lamp, refer to FSC
Specification SP0242 for the FT-2045 or FSC Specification 1505-008A for
the FT-2145.
NOTE: Other manufacturers UV/IR Test Lamps should not be
utilized to test FSC Detectors; conversely, the FT-2045 and FT-2145
Test Lamps should not be utilized for testing other manufacturer’s
Detectors.