Calibration Handbook
80 Searchline Excel
Calibrate
Install
System Type
Shrt Range
The second line shows the current gas detector type: Short Range 5 - 40m (15 - 130ft), Medium
Range 20 - 120m (65 - 390ft) or Long Range 20 - 200m (65 - 650ft)
6. Press
, the Current Path Length in meters is displayed. Verify actual path distance (in meters)
between transmitter and receiver.
Path Length
23
Minimum and maximum path length entry options for each gas detector are:
Gas Detector Type Minimum Range Maximum Range Step Size
Short Range 4m / 16ft 40m / 131ft 1m / 3ft
Medium Range 20m / 66ft 120m / 394ft 1m / 3ft
Long Range 20m / 66ft 200m / 656ft 1m / 3ft
7. When finished press Enter. Self-test routine is started display shows following message:
Self Test
Please Wait
When test is successful following message is displayed:
Checks Passed
The screen then changes to show a display similar to the following.
The first line of the display shows the magnitude of the current signal level as a horizontal bar graph - SIG:
The second line of the display shows the magnitude of the current target signal level as a horizontal bar
graph - TGT:
SIG:
TGT:
NOTE
a) The overall objective of alignment is to maximize the SIG level. Maximized SIG corresponds to optimal
alignment.
b) 

c) 
for the installation’s path length.
d) 

remain at its previous highest value. In order to initialize the gas detector the SIG level must be brought
back above the TGT level.