Installation Instruction VARIODYN
®
 D1 System 
 
26  FB 798663.GB0 / 05.19 
 110 … 230 V AC – Rated voltage 
A power supply cable is included in the delivery. Observe local standards and 
guidelines prior to operation. 
Alternatively, the connection can take place via the main switch unit (MSU). 
See chapter 6.3. 
Exception: DOM (Part No. 583361.22.UL and 583362.22.UL) 
 
 Fuses 
 
Device fuses F1 = 1.6 AT / 250 V and F2 = 5 AT / 250 V 
Never repair or bridge the device fuse that is installed or replace it 
with anything other than the stated type! 
 
 Two Wire Interface (TWI) 
 
Connection option for a time synchronisation module (TCM),a Contact-Interface-
Module (CIM),  a service PC, or an fire alarm control panel.  Do not connect 
second jack! 
 
A TWI-RS232 adapter (Part No. 583386.21) is also required for connecting the service PC  
and the FACP. 
 
 PA CH1/2 and PA CH3/4 (output to power amplifier) 
 
0 dB signal output for connection to a power amplifier (PA). 
 
Power amplifier (PA) 
Connection  PIN  Assignment of RJ45 socket for connection to a DOM 
 
Systematic input for channel 2 (CH2) 
Normal operation: + 24 V (12 V … 24 V), Aux (battery) supply  
error 0 V, mains (110 …230 V) supply error 24 V intermittent 
Systematic input for channel 1 (CH1) 
0 V reference potential for the connection to VARIODYN
®
 D1 
Ext. 24 V active  'Ext. amp enable' PIN monitored 
8  Ext. amp. enable 
Switch off channel 1 (CH1) and channel 2 (CH2)