CHAPTER 11: SUMMARIES OF PARAMETER SETTINGS
121 63-4528—04
PUMP Parameters
Table 11. Pump parameters
Parameter Explanation Settings
Factory
Setting
10-00 Circulative Control
0: No operation
1: Fixed Time Circulation (by time)
2: Fixed quantity circulation (by PID)
3: Fixed quantity control
4: Fixed Time Circulation+ Fixed quantity circulation
5: Fixed Time Circulation+ Fixed quantity control
0
10-01
Number of motors to be
connected
From only 1 and up to 8 motors 1
10-02
Operating time of each motor
(minutes)
0 to 65500 min 0
10-03
Delay Time due to the
Acceleration (or the Increment )
at Motor Switching
0.0 to 3600.0 sec 10
10-04
Delay Time due to the
Deceleration ( or the Decrement)
at Motor Switching (seconds)
0.0 to 3600.0 sec 10
10-05
Delay time while fixed quantity
circulation at Motor Switching
(seconds)
0.0 to 3600.0 sec 100
10-06
Frequency when switching
motors at fixed quantity
circulation (Hz)
0.00 to 600.00 Hz 6000
10-07
Action to do when Fixed Quantity
Circulation breaks down.
0: Turn off all output
1: Motors powered by mains electricity continues to
operate.
0
10-08
Frequency when stopping
auxiliary motor (Hz)
0.00 to 600.00 Hz 0