CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
131 63-4528—04
This parameter enables the VFDs to run in the forward/reverse Direction. It may be used to prevent a motor from running in a
direction that would consequently injure the user or damage the equipment.
If keypad is the source of frequency command, when Lv or Fault occurs the present frequency command will be saved in this
parameter.
Bit 0~3: F & H page unit and Pr.00-20 decimal display is supported up to 3 decimal places.
Bit 4~15: F & H page unit and Pr.00-20 unit display is supported up to 4 types of unit display.
User define is enabled when Pr.00-20 is not 0. The setting of Pr.00-20 corresponds to Pr.01.00 (Max. output frequency of the
drive).
Example: User define: 100.0%, Pr.01.00 = 60.00Hz
Pr.00.25 setting is 0021h; Pr.0026 setting is 100.0%
NOTE: In order to display as the setting in Pr.0025, please set up Pr.00.25 first and ensure Pr.00.26 is not set to 0.
a
00 - 17 Motor Operating Direction Control
Factory Setting: 0
Settings 0: Enable forward/ reverse
1: Disable reverse
2: Disable forward
00 - 18 Memory of Communication Frequency Command
Factory Setting: Read Only
Settings Read Only
00 - 19 User Defined Property
Factory Setting: 0
Settings B Bit 0~3: user define on decimal place
0000b: no decimal place
0001b: one decimal place
0010b: two decimal place
0011b: three decimal place
Bit 4~15: user define on unit
000xh: Hz
001xh: rpm
002xh: %
003xh: kg
00 - 20 Max. User Defined Value
Factory Setting: 0
Settings 0: Disable
0000B: 0~65535 (No decimal place in Pr.00-19 setting)
0001B: 0.0~6553.5 (One decimal place in Pr.00-19 setting)
0010B: 0.0~655.35 (Two decimal place in Pr.00-19 setting)
0011B: 0.0~65.536 (Three decimal place in Pr.00-19 setting)