CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
131 63-4528—04
• This parameter enables the VFDs to run in the forward/reverse Direction. It may be used to prevent a motor from running in a
direction that would consequently injure the user or damage the equipment.
• If keypad is the source of frequency command, when Lv or Fault occurs the present frequency command will be saved in this
parameter.
• Bit 0~3: F & H page unit and Pr.00-20 decimal display is supported up to 3 decimal places.
• Bit 4~15: F & H page unit and Pr.00-20 unit display is supported up to 4 types of unit display.
• User define is enabled when Pr.00-20 is not 0. The setting of Pr.00-20 corresponds to Pr.01.00 (Max. output frequency of the
drive).
Example: User define: 100.0%, Pr.01.00 = 60.00Hz
Pr.00.25 setting is 0021h; Pr.0026 setting is 100.0%
NOTE: In order to display as the setting in Pr.0025, please set up Pr.00.25 first and ensure Pr.00.26 is not set to 0.
a
00 - 17 Motor Operating Direction Control
Factory Setting: 0
Settings 0: Enable forward/ reverse
1: Disable reverse
2: Disable forward
00 - 18 Memory of Communication Frequency Command
Factory Setting: Read Only
Settings Read Only
00 - 19 User Defined Property
Factory Setting: 0
Settings B Bit 0~3: user define on decimal place
0000b: no decimal place
0001b: one decimal place
0010b: two decimal place
0011b: three decimal place
Bit 4~15: user define on unit
000xh: Hz
001xh: rpm
002xh: %
003xh: kg
00 - 20 Max. User Defined Value
Factory Setting: 0
Settings 0: Disable
0000B: 0~65535 (No decimal place in Pr.00-19 setting)
0001B: 0.0~6553.5 (One decimal place in Pr.00-19 setting)
0010B: 0.0~655.35 (Two decimal place in Pr.00-19 setting)
0011B: 0.0~65.536 (Three decimal place in Pr.00-19 setting)