CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
63-4528—04 132
Pr.00-21 will show user defined value when Pr.00-20 is not set to 0.
It is used to set the source of the master frequency in HAND mode.
It is used to set the source of the operation frequency in HAND mode.
Pr.00-14 and 00-15 are for the settings of frequency source and operation source in AUTO mode. Pr.00-23 and 00-24 are for
the settings of frequency source and operation source in HAND mode. The AUTO/HAND mode can be switched by the keypad
or multi-function input terminal (MI).
The factory setting of frequency source or operation source is for AUTO mode. It will return to AUTO mode whenever power on
again after power off. If there is multi-function input terminal used to switch AUTO/HAND mode. The highest priority is the
multi-function input terminal. When the external terminal is OFF, the drive won’t receive any operation signal and can’t execute
JOG.
00 - 21 User Defined Value
Factory Setting: Read Only
Settings Read Only
00 - 22 Local/Remote Selection
Factory Setting: 0
Settings 0: Standard HOA
1: LOC/REM not maintain
2: REM maintain
3: LOC maintain
4: LOC/REM maintain
a
00 - 23 Source of the Master Frequency Command (HAND)
Factory Setting: 0
Settings 0: Digital keypad
1: RS-485 serial communication
2: External analog input (Pr.03-00)
3: External UP/DOWN terminal
6: CANopen communication card
8: Communication card (no CANopen card)
a
00 - 24 Source of the Operation Command (HAND)
Factory Setting: 0
Settings 0: Digital keypad
1: External terminals. Keypad STOP disabled.
2: RS-485 serial communication. Keypad STOP disabled.
3: CANopen communication card
5: Communication card (not including CANopen card)