CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
157 63-4528—04
Example of crane function
30
Output when Frequency ≤ Pr.02-
32
Active when frequency is ≤ Pr.02-32.
31 Y-connection for the Motor Coil Active when PR.05-24 is less than Pr.05-23 and time is more than Pr.05-25.
32 D-connection for the Motor Coil Active when PR.05-24 is higher than Pr.05-23 and time is more than Pr.05-25.
33
Zero Speed (actual output
frequency)
Active when the actual output frequency is 0. (the drive should be at RUN mode)
34
Zero Speed with Stop (actual
output frequency)
Active when the actual output frequency is 0 or Stop.
35
Error Output Selection 1 (Pr.06-
22)
Active when Pr.06-22 is ON.
36
Error Output Selection 2 (Pr.06-
23)
Active when Pr.06-23 is ON.
37
Error Output Selection 3 (Pr.06-
24)
Active when Pr.06-24 is ON.
38
Error Output Selection 4 (Pr.06-
25)
Active when Pr.06-25 is ON.
40
Speed Attained (including zero
speed)
Active when the output frequency reaches frequency setting or stop
44 Low Current Output This function needs to be used with Pr.06-61 ~ Pr.06-63
45
UVW Magnetic Contactor
enabled
47 Brake Released at Stop
When drive stops, the corresponding multi-function terminal will be ON if the
frequency is less than Pr.02-32. After it is ON, it will be OFF when brake delay time
exceeds Pr.02-30.
50 Output for CANopen control For CANopen communication output
51 Output for RS-485 For RS-485 output
52 Output for communication card
For Modbus TC/IP Communication Card, Ethernet I/P Communication Card, and
communication control to do output
M33643
TIME
RUN
02-30
FREQUENCY
COMMAND
MULTI -FUNCTION
OUTPUT MO 47
FREQUENCY
COMMAND
<
02-32
RUN