CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
63-4528—04 168
When changing the input mode, please check if the switch of external terminal (SW3, SW4) corresponds to the setting of
Pr.03-25~03-26.
P.03-27 shows the external multi-function output terminal used by PLC
For Example:
If the value of Pr.02-28 displays 0002h (Hex), it means AFM1and AFM2 are used by PLC.
Settings 0: 0-10V
1: 0-20mA
2: 4-20mA
a
03 - 26 ACI Selection
Factory Setting: 0
Settings 0: 4-20mA
1: 0-10V
2: 0-20mA
a
03 - 27 Display Status of PLC Output Terminal
Factory Setting: 0
Settings 0~65535
Monitor the status of PLC analog output terminals
03 - 28 AFM2 0-20mA Output Selection
Factory Setting: 0
Settings 0: 0-20mA output
1: 4-20mA output
03 - 29 AFM1 DC Output Setting Level
03 - 30 AFM2 DC Output Setting Level
Factory Setting: 0.00
Settings 0.00~100.00%
03 - 32
AI calculated selection
Factory Setting:1
Settings 0 ~ 7
M33663
22222222
15 14 13 12 11 10 9 8
WEIGHTS
BIT
15 14 13 12 11 10 9 8
22222222
76543210
7654321
NOTE
2
7
128
2
3
8
2
6
64
2
2
4
2
5
32
2
1
2
2
4
16
2
0
1
0
0 ON
1 OFF
AFM 1
AFM 2
WEIGHTS
BIT
22222222
00000010
7654321
0
0 NOT USED BY PLC
1 USED BY PLC
AFM 1
AFM 2
DISPLAY VALUE
2 1x 2
1
+ 0 x2
0
BIT 1x2
1
+ BIT 0 x2
0