CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
167 63-4528—04
• It is used to adjust the analog voltage level (Pr.03-17) that terminal AFM outputs.
• This parameter is set the corresponding voltage of the analog output 0.
a
03 - 21 Gain for Analog Output 2 (AFM2)
Factory Setting: 100.0
Settings 0~500.0%
a
03 - 22 Analog Output 2 Value in REV Direction (AFM2)
Factory Setting: 0
Settings 0: Absolute value in REV direction
1: Output 0V in REV direction; output 0-10V in FWD direction
2: Output 5-0V in REV direction; output 5-10V in FWD direction
a
03 - 23 Display Low-Pass Filter AFM1, AFM1 Filter
a
03 - 24 Display Low-Pass Filter AFM2, AFM2 Filter
Factory Setting: 0
Settings 0.001~65.535 seconds
a
03 - 25 AVI1 Selection
Factory Setting: 0
0V
(0mA)
M33662
03-19 0
03- 22 0
03 -15
03 -18
03 -21
10V (20 mA)
03-19 1
03- 22 1
10V (20 mA)
0V
(0mA)
03-19 2
03- 22 2
FREQUENCY
FREQUENCY
10V (20 mA)
5V
(12mA)
Selections for the analog output direction