CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
63-4528—04 166
• This parameter determines the behAVI1or when ACI is lost.
• When Pr.03-26 is set to 1, it means ACI terminal is for 0-10V voltage input. At this moment, Pr.03-16 will be invalid.
• When setting is 1 or 2, it will display warning code “AnL” on the keypad. It will be blinking until the loss of the ACI signal is
recovered or drive is stop
a
03 - 16 Loss of the ACI Signal
Factory Setting: 0
Settings 0: Disable
1: Continue operation at the last frequency
2: Decelerate to stop
3: Top immediately and display ACE
a
03 - 17 Multi-function Output 1 (AFM1)
a
03 - 18 Gain for Analog Output 1 (AFM1)
Factory Setting: 0
Factory Setting: 100.0
a
03 - 19 Analog Output 1 Value in REV
Direction (AFM1)
Factory Setting: 0
a
03 - 20 Multi-function Output 2 (AFM2)
Factory Setting: 2
Settings 0~23
Table 2. Function Chart
Settings Functions Descriptions
0 Output frequency (Hz) Max. frequency Pr.01-00 is regarded as 100%.
1 Frequency command (Hz) Max. frequency Pr.01-00 is regarded as 100%.
2 Motor speed (Hz) 600Hz is regarded as 100%
3 Output current (rms) (2.5 X rated current) is regarded as 100%
4 Output voltage (2 X rated voltage) is regarded as 100%
5 DC Bus Voltage 450V (900V)=100%
6 Power factor -1.000~1.000=100%
7 Power Rated power is regarded as 100%
8 Output torque Full-load torque is regarded as 100%
9 AVI1 % 0~10V=0~100%
10 ACI % 0~20mA=0~100%
22
Analog output for communication card
For communication output (CMC-MOD01, CMC-EIP01, CMC-PN01, CMC-
DN01)
23
Constant voltage output
Voltage output level can be controls by Pr.03-29 and Pr03-33.
0~100% of Pr.03-29 corresponds to 0~10V of AFM1.