CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
165 63-4528—04
• These input delays can be used to filter noisy analog signal
• When the setting of the time constant is too large, the control will be stable but the control response will be slow. When the
setting of time constant is too small, the control response will be faster but the control may be unstable. To find the optimal
setting, please adjust the setting according to the control stable or response status.
• When Pr.03-15 is set to 0 and the analog input setting is the same, the priority for AVI1, ACI and AVI2 are AVI1>ACI>AVI2.
Repartir
a
03 - 09 Analog Input Gain 1 (AVI1)
a
03 - 10 Analog Input Gain 2 (ACI)
a
03 - 11 Analog Positive Input Gain 3 (AVI2)
a
03 - 12 Analog Input Filter Time (AVI1)
a
03 - 13 Analog Input Filter Time (ACI)
a
03 - 14 Analog Input Filter Time (AVI2)
Factory Setting: 0.01
Settings 0.00~20.00 seconds
a
03 - 15 Addition Function of the Analog Input
Factory Setting: 0
Settings
0: Disable (AVI1, ACI, AVI2)
1: Enable
M33661
VOLTAGE
FREQUENCY
F COMMAND [(AY
±
BIAS)
*
GAIN]
*
F COMMAND: THE CORRESPONDING FREQUENCY FOR 10V OR 20mA
AY: 10 OR 16mA
BIAS: PR.03-03, PR. 03-04, PR. 03-05
GAIN: PR.03-09, PR. 03-10, PR. 03-11
F MAX (01-00)