CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
63-4528—04 164
• It is used to set the corresponding ACI voltage of the external analog input 0.
• It is used to set the corresponding AVI2 voltage of the external analog input 0.
• The relation between external input voltage/current and setting frequency: 0~10V (4-20mA) corresponds to 0-60Hz.
• In a noisy environment, it is advantageous to use negative bias to provide a noise margin. It is recommended NOT to use less
than 1V to set the operation frequency.
a
03 - 04 Analog Input Bias 1 (ACI)
Factory Setting: 0
Settings -100.0~100.0%
a
03 - 05 AVI2 Analog Positive Input Bias
Factory Setting: 0
Settings -100.0~100.0%
a
03 - 06 Positive/negative Bias Mode (AVI1)
a
03 - 07 Positive/negative Bias Mode (ACI)
a
03 - 08 Positive/negative Bias Mode (AVI2)
Factory Setting: 0
Settings 0: Zero bias
1: Lower than bias=bias
2: Greater than bias=bias
3: The absolute value of the bias voltage while serving as the center
4: Serve bias as the center
M33660
POSITIVE
BIAS
BIAS
BIAS
03 -11 ~ 03 -1 4 GAIN IS POSITIVE
0 ZERO BIAS
1 LOWER THAN BIAS BIAS
2 GREATER THAN BIAS BIAS
3 THE ABSOLUTE VALUE OF
THE BIAS VOLTAGE WHILE
SERVING AS THE CENTER
4 SERVE BIAS AS THE CENTER
NEGATIVE
BIAS
03-00 TO 03-02
-10V -9 -8 -7 -6 -5 -4 -3 -2 -1 10V123456789