CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
63-4528—04 164
It is used to set the corresponding ACI voltage of the external analog input 0.
It is used to set the corresponding AVI2 voltage of the external analog input 0.
The relation between external input voltage/current and setting frequency: 0~10V (4-20mA) corresponds to 0-60Hz.
In a noisy environment, it is advantageous to use negative bias to provide a noise margin. It is recommended NOT to use less
than 1V to set the operation frequency.
a
03 - 04 Analog Input Bias 1 (ACI)
Factory Setting: 0
Settings -100.0~100.0%
a
03 - 05 AVI2 Analog Positive Input Bias
Factory Setting: 0
Settings -100.0~100.0%
a
03 - 06 Positive/negative Bias Mode (AVI1)
a
03 - 07 Positive/negative Bias Mode (ACI)
a
03 - 08 Positive/negative Bias Mode (AVI2)
Factory Setting: 0
Settings 0: Zero bias
1: Lower than bias=bias
2: Greater than bias=bias
3: The absolute value of the bias voltage while serving as the center
4: Serve bias as the center
M33660
POSITIVE
BIAS
BIAS
BIAS
03 -11 ~ 03 -1 4 GAIN IS POSITIVE
0 ZERO BIAS
1 LOWER THAN BIAS BIAS
2 GREATER THAN BIAS BIAS
3 THE ABSOLUTE VALUE OF
THE BIAS VOLTAGE WHILE
SERVING AS THE CENTER
4 SERVE BIAS AS THE CENTER
NEGATIVE
BIAS
03-00 TO 03-02
-10V -9 -8 -7 -6 -5 -4 -3 -2 -1 10V123456789

Related product manuals