CHAPTER 12: DESCRIPTION OF PARAMETER SETTINGS
163 63-4528—04
03 Analog Input/Output Parameter ~ The parameter can be set during operation
When it is frequency command or TQC speed limit, the corresponding value for 0~±10V/4~20mA is 0 – max. output frequency
(Pr.01-00)
It is to set the corresponding AVI1 voltage of the external analog input 0.
a
03 - 00 Analog Input 1 (AVI1)
Factory Setting: 1
a
03 - 01 Analog Input 2(ACI)
Factory Setting: 0
a
03 - 02 Analog Input 3 (AVI2)
Factory Setting: 0
Settings
0: No function
1: Frequency command
4: PID target value (Refer to Group 8)
5: PID feedback signal (Refer to Group 8)
6: PTC thermistor input value
11: PT100 thermistor input value
12~17: Reserved
a
03 - 03 Analog Input Bias 1 (AVI1)
Factory Setting: 0
Settings -100.0~100.0%
NEGATIVE TORQUE
POSITIVE TORQUE
FORWARD
03
-
00~02 9
REGENERATIVE
TORQUE LIMIT
03
-
00~02 7
POSITIVE
TORQUE LIMIT
03
-
00~02 9
REGENERATIVE
TORQUE LIMIT
03
-
00~02 10
POSITIVE/ NEGATIVE
TORQUE LIMIT
03
-
00~02 10
POSITIVE/ NEGATIVE
TORQUE LIMIT
03
-
00~02 8
NEGATIVE
TORQUE LIMIT
REVERSE